RE-9256 RP

  • 20 X 4 Dot Matrix LCD display.
  • Alphanumeric keypads.
  • RS 485 Communication for Network Repeater.
  • System ON, AC ON, Battery ON, Charger ON indications.
  • Lamp test facility.
  • Maximum 16 panels including repeater can be connected in a Single Network via RS-485.
  • Repeater Panel can monitor the status of RE-900 series panels via RS-485 Network communication.
  • User can Disable / Enable the Zone of Fire Alarm Control Panel Connected in network.
Category: Tag: Brand:

Commitment to Quality

Built with excellence, delivered with trust.

Customer Satisfaction

Your happiness is our highest success.

Standard Designed

Crafted to meet industry standards with perfection.

  • Ravel Indian Manufacturer, International standard.
  • Operates on RS-485 communication.
  • Repeats all the parameters of the main FACP.
  • Electrical Specification

    AC Power :
    120-220 VAC,60/ 50 Hz

    Battery (Lead Acid only)
    Charging Current: Constant Voltage – 27.6v @ 0.5A (Max.).
    24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)
    System Quiescent Current: 70mA

    Operating Condition
    Operating Temperature : 0 – 49° C / 32-120° F.
    Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.

    Notification Appliance Circuits (Sounder Circuit)
    Operating Nominal Voltage: 24 VDC
    Sounder (NAC) output: 0.5A
    End-Of-Line Resistor: 4.7K, 1/4watt

    Potential Free Relay Contact
    Type : Form C
    No of Relays : 1
    Relay Contact Rating: 2 Amps @ 30 VDC,
    0.5 Amps @125 VAC,
    Battery (Lead Acid only)
    Charging Current: Constant Voltage – 27.6v @ 0.5A (Max.).
    24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)
    System Quiescent Current: 70mA

     

    Mechanical Specification

    Dimensions : (350W X 300H X 100D)
    Color : White
    Construction : 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish
    IP Rating : IP50
    Cable Entry : 11xø19mm Knockout in top of the cabinet

     

    Compatible Devices

    Models Description
    RE-900 series Fire Alarm Control Panel

     

    Ordering Information

    Model Description
    Up to 32 Zones RE- 9032RP
    Up to 128 Zones RE- 9128RP
    Up to 256 Zones RE-9256RP

    NOTE:
    RE-9XXXRP →RE-900RP Series Repeater Panel
    XXX → 32Zone , 128Zone, 256Zone